Schneider Electric / Eurotherm Dimension 8725 PID Controller
The Eurotherm Dimension 8725 is a versatile PID (Proportional-Integral-Derivative) controller designed for precise temperature and process control in a wide range of industrial applications. This controller features advanced algorithms and configurable I/O options to optimize control performance and ensure process stability.
- Model
- Schneider Electric / Eurotherm 8725
- Calibration
- Available on request
- Price
- $310
- Status
- In stock
- RFQ ref
- 8725
This unit
The Schneider Electric Eurotherm Dimension 8725 is a modular multi-loop PID controller engineered for precision temperature and process control in industrial automation systems. This DIN-rail mounted instrument delivers up to 8 independent PID control loops with configurable control modes (PID, PI, PD, P, I) and auto-tuning functionality. The unit integrates 18 analog inputs, 12 analog outputs, 32 digital I/O points, and 8 programmers to support complex sequential and event-driven control strategies across demanding process applications.
Technical Specifications
Control Architecture- Multi-loop PID control with 8 independent loops
- Configurable control modes: PID, PI, PD, P, or I
- Auto-tuning for loop parameter optimization
- Sequential and digital control with setpoint ramping
- Multiple alarm strategies and math function processing I/O Configuration
- 18 analog inputs
- 12 analog outputs
- 32 digital I/O channels
- 8 programmers Communication & Interfaces
- EIA-232, EIA-422, and IEEE-488 ports on single unit
- Real-time clock and memory card data storage
- Eurotherm iTools configuration software
- Graphical operator interface with user-configurable display Electrical
- Supply: 24 V DC (bus and field power)
- Operating voltage range: 20.4 to 28.8 V DC
- Bus current: 32.4 mA typical
- Field current: 8.4 mA (minimum) to 210.1 mA (maximum)
- Maximum consumption: 1.43 W at 24 V DC
- Channel-to-bus isolation: 1500 V AC
- Channel-to-ground isolation: 1500 V AC Physical & Environmental
- Mounting: TH35-7.5 or TH35-15 DIN rail (IEC 60715)
- Dimensions: 121 mm H × 15 mm W × 80 mm D
- Weight: 0.077 kg
- IP20 rating
- Operating temperature: -20 to 60 °C
- Storage temperature: -40 to 85 °C
- Relative humidity: 5 to 95% non-condensing
- Operating altitude: 0 to 2000 m undeerated; 2000 to 5000 m deerated
- Vibration: 1 g without accessory, 2 g with accessory
- Shock: 15 g for 11 ms
- Pollution degree: 2
Certifications CE, UKCA, CULus, RCM, EAC. Pending: ATEX Zone 2, IECEx Zone 2, CCC Ex Zone 2. Compliance: EN/IEC 61131-2, EN 61010-2-201, UL 61010-2-201, IACS E10, EN/IEC 61000-6-5, EN/IEC 61850-3, EN/IEC 60079-0, EN 50155, EN 50121-4, EN 50121-5. Directives: 2014/30/EU, 2014/34/EU.
Specifications
| Parameter | Value |
|---|---|
| Voltage / Current Range | 20.4–28.8 V DC, 32.4 mA (bus), 8.4–210.1 mA (field) |
Schneider Electric / Eurotherm 8725 — Repair & Calibration Service
Aumictech offers NIST-traceable calibration and repair for the Schneider Electric / Eurotherm 8725. Calibration covers I/O channel accuracy per specification, analog output and input calibration to rated accuracy, and functional communication interface test (serial, Ethernet, fieldbus). All calibrations ship with a NIST-traceable certificate. Turnaround is typically 1–3 business days after receipt.
Common Schneider Electric / Eurotherm 8725 faults: blown I/O fuses, failed analog modules, power supply capacitor failure. Common faults include blown I/O protection fuses, failed analog I/O modules, power supply capacitor failure, and serial or Ethernet communication port damage.
Schneider Electric / Eurotherm 8725 price
This Schneider Electric / Eurotherm 8725 is listed at $310. Calibration is available separately from $450. Contact us for volume pricing or if you need multiple units.
Schneider Electric / Eurotherm 8725 calibration cost
NIST-traceable calibration for the Schneider Electric / Eurotherm 8725 is $450 (standard — pass/fail certificate and calibration sticker) or $650 (full measured data at every test point, reference standards documented, traceability chain included). Calibration for this instrument covers I/O channel accuracy per specification, analog output and input calibration to rated accuracy, and functional communication interface test (serial, Ethernet, fieldbus). Turnaround is 1 to 3 business days after receipt. See full calibration details →