OneAC HoldUp HU200 Ride-Through Power Source

Chloride / OneAC Power Supply Accessories. Voltage: ** 120 V (USA specified)., Voltage: ** Sine wave..

Model
Chloride / OneAC HU200
Calibration
Available on request
Price
$1,100
Status
In stock
RFQ ref
HU200
View cart
Prefer to talk? Call +1 (484) 841-9341

This unit

The Chloride / OneAC HoldUp HU200 is a ride-through power source designed to offer uninterrupted power to critical equipment during brief power interruptions or voltage fluctuations. This device leverages stored energy to bridge gaps in power delivery, thereby preventing data loss and minimizing equipment downtime, making it suitable for sensitive electronic devices and industrial control systems.

Technical Specifications Power Conditioning:

  • Technology: Proprietary low-impedance technology.
  • Surge Voltage Withstand Capability: ANSI/IEEE C62.41 Category A & B, 6 kV/200 & 500 Amp, 100 kHz ringwave.
  • Surge Voltage Let-Through (Max): Less than 10 V Normal mode (L-N), less than 0.5 V Common mode (N-G) when subjected to 6 kV ANSI/IEEE.
  • Full Output Isolation: Achieved through proprietary transformer design integrating power conditioning and voltage conversion magnetics.
  • Virtual Kelvin Ground®: A patented grounding methodology that establishes a noise-free power environment. Electrical Characteristics:
  • Input Voltage: 120 V (USA specified).
  • Input Frequency: 60 Hz (USA specified).
  • Output Voltage: 120 V (USA specified).
  • Output Receptacles: "T-slot" output connector accepts either 5-15P or 5-20P plugs. Additional receptacle options may be available.
  • ONBoost Functionality: Boosts output voltage 11% above input voltage if input is between -21% and -15% of nominal. Performance:
  • Transfer Time (Typical/Max): < 3.0 / 3.5 milliseconds.
  • On-Battery Output Voltage: Sine wave.
  • Load Power Factor Range (Crest Factor): UPS .65 to 1.0 (3). Supports loads rated 0.5 to 1.0 (<5).
  • Typical Runtime at Full Load: Approximately 14 minutes (for a 60 Hz unit). Note: Actual runtime may vary based on application-specific conditions and system load. Interfaces:
  • Communications: Intelligent serial communications for advanced diagnostics and remote management. Includes MopUPS software and cable for network shutdown and remote management. Optional USB and SNMP available. Physical Characteristics:
  • Dimensions (H x W x D): 3.5 in x 17.25 in x 19.5 in (9 cm x 44 cm x 50 cm).
  • Design: Compact, slim-line design to conserve space. Can be rackmountable (with a 23" rackmount option available).
  • Battery Replacement: Patented battery pack allows for replacement in under a minute, without tools, training, or downtime. On-site, on-line replaceable battery. Compatibility:
  • Voltage and Frequency: Designed for 120V, 60Hz North American power systems.
  • Plug Compatibility: "T-slot" output connector accepts standard NEMA 5-15P and 5-20P plugs.
  • Software: Compatible with MopUPS software for network shutdown and remote management. Environmental and Safety:
  • Operating Temperature: Batteries should not be kept in storage for periods exceeding 6 months at 25°C without being recharged; recharge at least once every 4 months.
  • Battery Disposal: Batteries must be disposed of in accordance with regulations for toxic and harmful waste.
  • Safety: Contains capacitors that represent a severe shock hazard, even when unplugged. No user-serviceable parts inside; servicing by qualified personnel only. Risk of electrical shock from batteries and high short-circuit intensity. Why Choose Aumictech for Chloride / OneAC HoldUp HU200? At Aumictech, we specialize in supplying high-end power protection equipment. Whether you need seamless ride-through power for critical industrial control systems, reliable protection for sensitive electronic devices, or solid solutions to prevent equipment downtime, our team ensures the Chloride / OneAC HoldUp HU200 delivers maximum performance for your application.

Chloride / OneAC HU200 — Repair & Calibration Service

Aumictech offers NIST-traceable calibration and repair for the Chloride / OneAC HU200. All calibrations are performed to NIST-traceable standards and ship with a certificate. Turnaround is typically 1–3 business days after receipt.

Standard Cal
$450
Pass/fail cert + NIST sticker
Cal with Data
$650
Full NIST cert with measured values

Chloride / OneAC HU200 price

This Chloride / OneAC HU200 is listed at $1,100. Calibration is available separately from $450. Contact us for volume pricing or if you need multiple units.

Chloride / OneAC HU200 calibration cost

NIST-traceable calibration for the Chloride / OneAC HU200 is $450 (standard — pass/fail certificate and calibration sticker) or $650 (full measured data at every test point, reference standards documented, traceability chain included). Turnaround is 1 to 3 business days after receipt. See full calibration details →