Lambda / TDK / EMI EMHP50-1000-D-42212
Lambda / TDK DC Power Supplies. Voltage: ** Up to 600 VDC, Current: ** 0–1000 A.
- Model
- Lambda / TDK EMHP50-1000-D-42212
- Calibration
- Available on request
- Price
- $11,500
- Status
- In stock
- RFQ ref
- EMHP50-1000-D-42212
This unit
The Lambda/TDK EMHP50-1000-D-42212 is a 20 kW regulated power supply built on SCR phase control topology for high-current DC applications. It delivers 0–1000 A output current with constant voltage and constant current modes, automatic crossover control, and ±0.1% line and load regulation. Forced air cooling, built-in RFI protection, and fully programmable operation make it suitable for applications demanding raw bulk power delivery. The unit features fully metered output with mode indicator lights, contactor-based interlock control, and lifting eye-bolt provisions for installation. Three-phase AC input accepts 440–480 VAC at 50/60 Hz. Output voltage capability extends up to 600 VDC. Transient response recovers to within 1% of final value in 200 ms under ±10% line variation or 50–100% load change. Output voltage stability holds ±0.05% for 8 hours under constant external conditions. Note: This model is not recommended for new designs; Genesys™ or GENESYS+™ series are preferred alternatives.
Technical Specifications
Model: EMHP50-1000-D-42212
Topology: Regulated SCR phase control
Output Power: 20 kW maximum
Output Voltage: Up to 600 VDC
Output Current: 0–1000 A
Input: Three-phase AC, 440–480 VAC ±10%, 50/60 Hz
Line Regulation: ±0.1%
Load Regulation: ±0.1%
Long-term Stability: ±0.05% over 8 hours
Transient Response: Recovery to 1% within 200 ms (±10% line or 50–100% load variation)
Output Ripple: 50 mV RMS (EMHP 10-1000 reference)
Cooling: Forced air
Efficiency: Up to 89%
Key Features
Constant Voltage / Constant Current with automatic crossover
Fully programmable control
Built-in RFI filtering for EMI compliance
Metered output with mode indicator lights
Contactor on/off interlock
Lifting eye-bolt for mechanical handling
Typical Applications
High-current DC power for industrial testing and process control
Raw bulk power delivery in manufacturing environments
Applications requiring tight voltage and current regulation
Compatibility & Integration Three-phase AC input design suits industrial facility power distribution. Programmable control enables integration into automated test and manufacturing systems. For new designs, TDK-Lambda recommends evaluation of Genesys™ or GENESYS+™ series.
Specifications
| Parameter | Value |
|---|---|
| Voltage / Current Range | 440–480 VAC input (three-phase, 50/60 Hz) |
Lambda / TDK EMHP50-1000-D-42212 — Repair & Calibration Service
Aumictech offers NIST-traceable calibration and repair for the Lambda / TDK EMHP50-1000-D-42212. All calibrations are performed to NIST-traceable standards and ship with a certificate. Turnaround is typically 1–3 business days after receipt.
Lambda / TDK EMHP50-1000-D-42212 price
This Lambda / TDK EMHP50-1000-D-42212 is listed at $11,500. Calibration is available separately from $450. Contact us for volume pricing or if you need multiple units.
Lambda / TDK EMHP50-1000-D-42212 calibration cost
NIST-traceable calibration for the Lambda / TDK EMHP50-1000-D-42212 is $450 (standard — pass/fail certificate and calibration sticker) or $650 (full measured data at every test point, reference standards documented, traceability chain included). Turnaround is 1 to 3 business days after receipt. See full calibration details →